Description
GENERAL
The R438 provides excellent generator regulation at +/-1% voltage variation. This regulator provides a unique feature which separates it self from the competition, Load Acceptance Module (LAM). When load is 1st placed on the generator set usually the engine and generator end struggles as load is placed. As frequency decreases below a preset threshold, and to avoid a possible generator down the LAM feature will decrease the voltage to either 13% or 25% until engine speed reaches nominal speed. Consequently this action will cause the active load to decrease about 25% to 50%. The good news the LAM is adjustable or it can be disabled altogether as the operator chooses. The AVR R438 supports CT droop input which enables generator to generator synchronizing.
BASIC SPECIFICATIONS
- Voltage sensing:
- Terminals 0-110 VAC: Voltage range 95 to 140 VAC, 1 phase
- Terminals 0-110 VAC: Voltage range 170 to 260 VAC, 1 phase
- Terminals 0-110 VAC: Voltage range 340 to 520 VAC, 1 phase
- Frequency:
- 50 or 60 hz
- Voltage Regulation
- +/- 1%
- SHUNT, AREP or PMG Excited
APPLICATIONS
- Can be used on LSA 42.3, LSA 42.2, LSA 44.2, LSA 44.3, LSA46.2 LSA46.3, LSA47.2, LSA 49.1, LSA 49.3, LSA 50.2 + Leroy Somer alternator frames
- Mainly used on SDMO, Kohler, Waukesha, Olympian, FG Wilson & Caterpillar generator sets
CORRESPONDING, ASSOCIATED & OBSOLETE PART NUMBERS
- Leroy Somer AEM110RE017
- Leroy Somer AEM110RE003
- Leroy Somer RS437
- FG Wilson 922-045
- SDMO 330410127
- SDMO 330410164